DB-SUA in housing: stairs, guarding and changes of level
The stair in a duplex and the communal stair are not justified with the same figures. Their balustrades are: the conditions against climbing and openings are the same throughout the building.

In this article
The short version
Stairs and guarding can go wrong for the same reason: the figures for a general-use stair are applied to the stair inside a duplex or a dwelling’s figures to the communal stair. We follow section SUA 1 of the Basic Document SUA (safety in use and accessibility) in its consolidated version of 14 June 2022, the Ministry’s annotated edition of 15 July 2024 and, for the strength of balustrades, DB SE-AE on actions. The rules are Spanish. The split between private and common stairs will be familiar from most codes.
Restricted or general use: the first question
Annex A defines restricted use as circulation areas or elements limited to at most 10 regular users. The definition includes «the inside of dwellings» and excludes the common areas of residential buildings. The Ministry’s comment leaves no room for argument: the inside of a dwelling is always restricted use, however many people live there. The common areas never are.
The common areas are the communal stairs, landings, entrance halls, car parks and corridors to storage rooms. And since annex A’s definition of public use does not mention residential use, they are general use but not public use. That difference decides the maximum riser.
The stair inside the dwelling
The stair in a duplex, a penthouse with a study above or a single-family house is restricted use and follows SUA 1 section 4.1, far shorter than the general-use rules:
- Each flight at least 0.80 m wide, which according to the Ministry’s comment must be kept along the landings too.
- Riser of 20 cm at most and going of 22 cm at least, measured in the direction of travel and without the projection of the step above.
- On curved stairs, the going is measured on the centre line if the stair is under 1 m wide and 50 cm from the narrow side if wider. It also measures at least 5 cm on the narrow side and at most 44 cm on the wide side.
- Split landings with 45º winders and open risers are allowed, with the treads overlapping by at least 2.5 cm.
- A balustrade on any open side.
The Ministry adds two clarifications. Mixed stairs, with straight and curved flights, are accepted for restricted use too. Alternating-tread stairs, the «ship» or «samba» type, are never valid. Inside the dwelling neither the 2R + G rule nor the minimum of three steps per flight applies: both belong to section 4.2.
The communal stair
The communal stair is general use (section 4.2) and here almost everything counts. The table sums up what it asks for in a residential building, depending on whether a lift is available as an alternative:
| Condition | With an alternative lift | Without an alternative lift | Clause |
|---|---|---|---|
| Clear width of flight | 1.00 m | 1.00 m | SUA 1, table 4.1 |
| Going on straight flights | At least 28 cm | At least 28 cm | SUA 1, 4.2.1 |
| Riser | Between 13 and 18.5 cm | Between 13 and 17.5 cm | SUA 1, 4.2.1 |
| Going and riser together | 54 ≤ 2R + G ≤ 70 cm | 54 ≤ 2R + G ≤ 70 cm | SUA 1, 4.2.1 |
| Maximum rise of a flight | 3.20 m | 2.25 m | SUA 1, 4.2.2 |
| Handrails | One side if it rises more than 55 cm. Both if wider than 1.20 m | Both sides, extended 30 cm at the ends on at least one | SUA 1, 4.2.4 |
Nosings are not allowed and every step between two floors has the same riser. Landings are at least 1 m long on the centre line and handrails sit between 90 and 110 cm high. For a lift to count as an alternative, the Ministry explains, it need not be next to the stair nor be accessible: it is enough that users can use it as such in normal conditions.
A worked example
An existing residential building without a lift, 3.00 m floor to floor. With 17 risers each would be 17.65 cm: too high, since without a lift the maximum is 17.5 cm. With 18 risers of 16.67 cm and a 28 cm going, 2R + G = 61.3 cm, within range. And as a flight cannot rise more than 2.25 m, each floor takes two flights of nine steps, 1.50 m each, with a landing between.
Changes of level: when guarding is needed
Section 3.1 requires guarding at changes of level, holes and openings, horizontal or vertical, balconies and windows, where the drop exceeds 55 cm. Exceptions apply where the construction makes a fall very unlikely and where a barrier is incompatible with the intended use. For the first, the Ministry mentions planted areas or water features. Its comment says this does not work where unsupervised children can be expected, which in housing all but rules it out.
What the balustrade must be like
Here is the exception that is easy to forget: section 3.2.3 applies its conditions «anywhere in residential buildings», stair and ramp balustrades included. The balustrade in the duplex meets the same rules as the one in the communal stair.
| Condition | Requirement | Clause |
|---|---|---|
| Height | 0.90 m if the drop is no more than 6 m and 1.10 m otherwise. At stair wells narrower than 40 cm, 0.90 m. Measured from the floor or, on stairs, from the pitch line of the steps | SUA 1, 3.2.1 |
| Climbability | No footholds projecting more than 5 cm between 30 and 50 cm high and no horizontal surfaces deeper than 15 cm between 50 and 80 cm | SUA 1, 3.2.3 a) |
| Openings | A 10 cm sphere must not pass. The triangle between step and balustrade is excepted if its bottom edge is no more than 5 cm from the pitch line | SUA 1, 3.2.3 b) |
| Strength | The horizontal force in DB SE-AE table 3.3, applied at 1.2 m or at the top edge if lower. That is 0.8 kN/m in general cases and 1.6 kN/m for categories C3, C4, E and F. For C5, 3.0 kN/m | SUA 1, 3.2.2 and SE-AE, 3.2 |
According to the Ministry’s comment, the risk is a child under six climbing over and falling, so climbability also covers fixed elements less than 50 cm from the guarding, such as a radiator. And although the gap between slab edge and balustrade is treated as a 10 cm opening, good practice advises keeping it to 3 cm.
A window is just another opening: if the sill is below guarding height and the drop exceeds 55 cm, it must be protected (figure 3.1).
In a refurbishment or change of use
In a refurbishment that keeps the use, the document applies to the elements the work alters, where that improves them. Existing conditions can never be made worse (rules 3 and 4 of section III). Rebuilding a stair inside a flat or replacing a balustrade means doing it to the document. Leaving an old building’s communal stair untouched does not.
Where compliance is not technically or economically viable or clashes with the building’s protection, alternative solutions may come as close as possible. Any limits on use are recorded in the as-built documentation. In a change of use, the Ministry allows flexibility where risk goes down and mentions turning a shop in a residential building into a dwelling. We cover the rest in retail to residential change of use.
What to write in the report
The justification of these clauses fits on one page if it is organised like this:
- Which stairs there are and the type of each: restricted use (inside the dwelling) or general use (common areas).
- Whether a lift serves as an alternative to the communal stair, since it sets the maximum riser, the rise per flight and the handrails.
- Going, riser, number of steps, rise of each flight and clear width, with the 2R + G check on general-use stairs.
- Drops of more than 55 cm, openings and low windows, with the height of each drop, which decides between 0.90 and 1.10 m.
- How balustrades meet the climbability and opening rules, inside the dwelling too. Their use category for the horizontal force.
- In a refurbishment, which elements are altered, the statement that existing conditions are not made worse and, if the document is not met, the solution adopted and why.
Common mistakes
- Justifying a duplex stair with the 28 cm going and three steps per flight or the communal stair with the 20 cm riser for restricted use.
- Taking an 18.5 cm riser in a building with no lift.
- 0.90 m balustrades on balconies with more than 6 m of drop.
- Balustrades with horizontal rails that act as a step between 30 and 50 cm. The same goes for planters and radiators next to them.
- A report saying «general-use stair» and drawings with 20 cm risers. We discuss cross-checking report and drawings in what a project report must contain.
How Archelo handles it
Archelo shows in its regulations view the DB-SUA figures for the project’s use, each with its clause: flight width, going and riser, flights, landings, handrails, guarding height and restricted-use stairs. It also checks whether the report justifies DB-SUA. It does not measure stairs or balustrades on the drawings nor decide whether a lift counts as an alternative: the architect justifies that. What it points out is where it still needs writing down.